ABB RELION 670 Series Technical Manual page 858

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
Table 495: SXSWI Output signals
Name
XPOS
EXE_OP
EXE_CL
SUBSTED
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
EEHEALTH
SWOPCAP
14.3.8.4
Settings
Table 496: SXSWI Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
InitialCount
0 - 20000
14.3.8.5
Operation principle
The users of the Circuit switch (SXSWI) are other functions such as for example, switch controller,
protection functions, autorecloser function, or a 61850 client residing in another IED or the
operator place. SXSWI executes commands, evaluates block conditions and evaluates different
852
Type
Description
GROUP SIGNAL
Group connection to CSWI for XCBR and XSWI
BOOLEAN
Executes the command for open direction
BOOLEAN
Executes the command for close direction
BOOLEAN
Indication that the position is substituted
BOOLEAN
Indication that the function is blocked for open commands
BOOLEAN
Indication that the function is blocked for close commands
BOOLEAN
Update of position indication is blocked
INTEGER
Apparatus position indication
BOOLEAN
Apparatus open position
BOOLEAN
Apparatus closed position
INTEGER
Operation counter value
INTEGER
Latest value of the error indication during command
INTEGER
External equipment health. 1=No warning or alarm, 2=Warning,
3=Alarm
INTEGER
Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C
Unit
Step
s
0.001
s
0.001
-
-
s
0.001
s
0.001
-
-
-
1
Default
Description
3.000
Supervision time for the apparatus to
move after a command
15.000
Allowed time for intermediate position
Not adaptive
Output resets when a new correct end
position is reached
0.200
Output pulse length for open command
0.200
Output pulse length for close command
Disconnector
Load Break, Disconnector, Grounding
Switch, HS Grounding. Switch
0
Initial number of operations (Initial count
value)
1MRK 502 066-UUS B
PID-6800-OUTPUTSIGNALS v4
PID-6800-SETTINGS v4
M16494-3 v6
Technical manual