Section 23
Injection equipment hardware
23.5
Technical data
23.5.1
Hardware
Table
1064:
Specifications
Case size
Weight
Burden, binary inputs
Burden, RIM injection
Burden, SIM injection
Burden, SIM injection with REX062
Burden, measuring transformer SIM
Burden, measuring transformer RIM
Installation category
Pollution degree
Table
1065:
Quantity
Auxiliary dc voltage, EL (input)
Power consumption
Auxiliary DC power in-rush
Table
1066:
Function
For machines with:
rated field voltage up to
static exciter with rated
supply voltage up to
Specifications
Case size
Table continues on next page
1368
REX060 Technical data
REX060 Power supply Technical data
REX061 Technical data
Range or values
800 V DC
1600 V 50/60 Hz
Values
6U, 1/2 19"; 8.81 x 9.65 x 10.51 inches (W x D x H)
17.64 lbs
BI 220 V: burden 0.4 W
BI 110 V: burden 0.2 W
BI 48 V: burden 0.1 W
< 10 VA at 100 V external disturbance
< 10 VA at 12 V ground fault voltage
0 VA at > 10% of maximum ground fault voltage
< 1 VA at 24 V ground fault voltage
< 60 mVA at 24 V; 87 Hz
< 60 mVA at 50 V; 113 Hz
III
2
Rated value
EL = (24 – 60) V
EL = (90 – 250) V
30 W
< 5 A during 0.1 s
Values
8.58 x 5.91 x 9.57 inches (W x D x H)
1MRK 502 066-UUS B
GUID-EDF13DA3-4658-4A20-8641-CD62F6C3BE0F v3
GUID-E7982609-5365-4D07-BE0B-09702B77454F v1
Nominal range
EL ±20%
EL ±20%
GUID-CDBAEE7B-3BCE-4401-B2DA-BF572CFF9DAE v3
Accuracy
-
-
Technical manual