ABB RELION 670 Series Technical Manual page 445

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
ANSI11000297 V1 EN-US
Figure 237: Block diagram of zone 1
The functionality included in zone 1:
Comparator to detect, if the operating impedance has entered inside zone 1 offset mho
characteristic.
All three phase-to-phase loops are implemented separately.
Forward and reverse reach values are provided in percentage of impedance base value at
generator.
Trip time delay is provided.
Comparator characteristics
The comparator consists of offset mho characteristics. Three individual comparators are provided
in the three phase-to-phase loops. The offset mho characteristic is as shown in figure 238.
Technical manual
BLOCK
BLKZ
Comparator
V3P
<
ZAB
I3P
EnableZone1
Z1Fw
Z1Rev
Comparator
<
ZBC
EnableZone1
Z1Fw
Z1Rev
Comparator
<
ZCA
EnableZone1
Z1Fw
Z1Rev
pickupZone1
Timer Logic
tripZone1
OR
tOpDelayZ1
opModetZ1
ANSI11000297_1.en.vsd
Section 7
Impedance protection
439