ABB RELION 670 Series Technical Manual page 1207

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Table 914: GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST
18.12.5
Settings
Table 915: GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
18.12.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
18.13
GOOSE function block to receive a measurand value
GOOSEMVRCV
18.13.1
Identification
Function description
GOOSE function block to receive a
measurand value
Technical manual
Type
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
-
-
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the integer values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
IEC 61850
identification
GOOSEMVRCV
Description
Integer output
Data valid for integer output
Communication valid for integer output
Test output
Default
Description
Disabled
Operation Disabled/Enabled
IEC 60617
identification
-
Station communication
PID-2529-OUTPUTSIGNALS v18
PID-2529-SETTINGS v18
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v2
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1
ANSI/IEEE C37.2
device number
-
Section 18