Section 14
Control
Name
189GITL
289GREL
289GITL
189OPTR
189CLTR
289OPTR
289CLTR
1289OPTR
1289CLTR
VP189TR
VP289TR
VP1289TR
14.2.12
Position evaluation POS_EVAL
14.2.12.1
Identification
Function description
Position evaluation
14.2.12.2
Functionality
Position evaluation (POS_EVAL) function converts the input position data signal POSITION,
consisting of value, time and signal status, to binary signals OPENPOS or CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
14.2.12.3
Function block
POS_EVAL
POSITION
IEC09000079_1_en.vsd
IEC09000079 V1 EN-US
Figure 431: POS_EVAL function block
824
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
IEC 61850
identification
POS_EVAL
OPENPOS
CLOSEPOS
Description
Switching of 189G is not allowed
Switching of 289G is allowed
Switching of 289G is not allowed
189 is in open position
189 is in closed position
289 is in open position
289 is in closed position
189 or 289 or both are in open position
189 and 289 are not in open position
Switch status of 189 is valid (open or closed)
Switch status of 289 is valid (open or closed)
Switch status of 189 and 289 are valid (open or closed)
IEC 60617
identification
-
1MRK 502 066-UUS B
GUID-F20A8939-E91E-44F6-920C-083E5D3FCDFD v2
GUID-3C4B9379-C861-406C-9295-0309014D548E v2
ANSI/IEEE C37.2
device number
-
GUID-C3D07B40-FF01-45C5-A083-EED5643A5FCC v4
GUID-B5EF4A28-9C9F-4558-8CD6-453FB480314B v2