ABB RELION 670 Series Technical Manual page 513

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
8.6.4
Signals
Table 242: SDEPSDE (67N) Input signals
Name
I3P
V3P
BLOCK
BLKTR
BLKTRDIR
BLKNDN
BLKVN
Table 243: SDEPSDE (67N) Output signals
Name
TRIP
TRDIRIN
TRNDIN
TRVN
PICKUP
PUDIRIN
PUNDIN
PUVN
PUFW
PUREV
CND
VNREL
Technical manual
Type
Default
Description
GROUP
-
Group signal for current
SIGNAL
GROUP
-
Group signal for voltage
SIGNAL
BOOLEAN
0
Blocks all the outputs of the function
BOOLEAN
0
Blocks the trip outputs of the function
BOOLEAN
0
Blocks the directional operate outputs of the function
BOOLEAN
0
Blocks the Non directional current residual outputs
BOOLEAN
0
Blocks the Non directional voltage residual outputs
Type
Description
BOOLEAN
General trip of the function
BOOLEAN
Trip of the directional residual over current function
BOOLEAN
Trip of non directional residual over current
BOOLEAN
Trip of non directional residual over voltage
BOOLEAN
General pickup of the function
BOOLEAN
Pickup of the directional residual over current function
BOOLEAN
Pickup of non directional residual over current
BOOLEAN
Pickup of non directional residual over voltage
BOOLEAN
Pickup of directional function for a fault in forward direction
BOOLEAN
Pickup of directional function for a fault in reverse direction
INTEGER
Direction of fault. A general signal common to all three mode of
residual over current protection
BOOLEAN
Residual voltage release of operation of all directional modes
Section 8
Current protection
PID-3892-INPUTSIGNALS v6
PID-3892-OUTPUTSIGNALS v6
507