ABB RELION 670 Series Technical Manual page 1253

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
21.1.3
Operation principle
21.1.3.1
General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time the clock is
intended to have. Clock accuracy indicates the increase in error, that is, the time gained or lost by
the clock. A disciplined clock knows its own faults and tries to compensate for them.
Design of the time system (clock synchronization)
The time system is based on software and hardware clocks that run independently from each
other. See figure
External
Synchronization
sources
Off
LON
SPA
Min. pulse
GPS
SNTP
DNP
IRIG-B
PPS
Off
GPS
IRIG-B
PPS
IEC08000287 V2 EN-US
Figure 629: Design of the time system (clock synchronization)
All time tagging is performed by the software clock. When, for example, a status signal is changed
in the protection system of a function based on the free running hardware clock, the event is time
tagged by the software clock when it reaches the event recorder. The hardware clock can thus run
independently.
The echo mode of differential protection is based on the hardware clock. Thus, there is no need to
synchronize the hardware clock and the software clock.
Technical manual
629
Time-
Regulator
(Setting,
see
SW-time
technical
reference
manual)
Time-
Regulator
(fast or slow)
Time tagging and general synchronisation
Protection
Comm-
Events
and control
unication
functions
Connected when GPS-time is
used for differential protection
Synchronization for differential protection
(ECHO-mode or GPS)
HW-time
Diff.-
A/D
comm-
converter
unication
Section 21
Basic IED functions
M11346-77 v1
M11346-80 v3
GUID-E2B9E81C-5733-4521-B27F-BF33E05CCFB0 v6
Trans-
ducers*
*IEC 61850-9-2
IEC08000287-2-en.vsd
IP12360-1 v4
1247