Section 14
Control
Time diagrams
There are two timers for supervising of the execute phase,
tStartMove supervises that the primary device starts moving after the execute output pulse is
tIntermediate defines the maximum allowed time for intermediate position. Figure
sent.
explains these two timers during the execute phase.
EXE_CL
OPENPOS
CLOSEPOS
tStartMove timer
tIntermediate timer
IEC05000097 V1 EN-US
Figure 451: The timers tStartMove and tIntermediate
The timers
the primary equipment. Note that the output pulses for open and close command can have
different pulse lengths. The pulses can also be set to be adaptive with the configuration
parameter
AdaptivePulse parameter will have effect on both execute output pulses.
854
It is always possible to make a substitution, independently of the position
indication and the status information of the I/O board. When substitution is
enabled, the other signals related to the position follow the substituted position.
The substituted values are stored in a non-volatile memory. If the function is
blocked or blocked for update when the substitution is released, the position value
is kept the same as the last substitution value, but the quality is changed to
"questionable, old data", indicating that the value is old and not reliable.
When the position of the SXSWI is substituted, its IEC61850-8-1 data object is
marked as "substituted", in addition to the substituted quality, but the position
quality of the connected SCSWI is not dependent on the substitution indication in
the quality, so it does not show that it is derived from a substituted value.
Close pulse duration
t1
tStartMove
tOpenPulse and tClosePulse are the length of the execute output pulses to be sent to
AdaptivePulse . Figure
452
tStartMove and tIntermediate .
t2
tIntermediate
shows the principle of the execute output pulse. The
1MRK 502 066-UUS B
AdaptivePulse = TRUE
if t1 > tStartMove then
"switch-not-start-moving"
attribute in 'cause' is set
if t2 > tIntermediate then
"persisting-intermediate-state"
attribute in 'cause' is set
en05000097.vsd