Section 16
Monitoring
Name
Values (Range)
UnderTrigLe09
0 - 200
OverTrigOp09
Disabled
Enabled
OverTrigLe09
0 - 5000
NomValue10
0.0 - 999999.9
UnderTrigOp10
Disabled
Enabled
UnderTrigLe10
0 - 200
OverTrigOp10
Disabled
Enabled
OverTrigLe10
0 - 5000
A2RADR to A4RADR functions have the same Non group settings (basic) as A1RADR but with
different numbering:
A2RADR: Operation11 to Operation20
A3RADR: Operation21 to Operation30
A4RADR: Operation31 to Operation40
A2RADR to A4RADR functions have the same Non group settings (advanced) as A1RADR but with
different numbering (examples given in brackets):
A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)
A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31)
Table 779: B1RBDR Non group settings (basic)
Name
Values (Range)
TrigDR01
Disabled
Enabled
SetLED01
Disabled
Pickup
Trip
Pickup and Trip
TrigDR02
Disabled
Enabled
SetLED02
Disabled
Pickup
Trip
Pickup and Trip
TrigDR03
Disabled
Enabled
Table continues on next page
1072
Unit
Step
Default
%
1
50
-
-
Disabled
%
1
200
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
Unit
Step
Default
-
-
Disabled
-
-
Disabled
-
-
Disabled
-
-
Disabled
-
-
Disabled
1MRK 502 066-UUS B
Description
Under trigger level for analog channel 9 in
% of signal
Use over level trigger for analog channel 9
(on) or not (off)
Over trigger level for analog channel 9 in %
of signal
Nominal value for analog channel 10
Use under level trigger for analog channel
10 (on) or not (off)
Under trigger level for analog channel 10 in
% of signal
Use over level trigger for analog channel 10
(on) or not (off)
Over trigger level for analog channel 10 in
% of signal
GUID-E05EEC82-CB90-4E73-B9C9-4C16FD95FCBF v1