ABB RELION 670 Series Technical Manual page 428

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
C
stat
ANSI11000008 V1 EN-US
Figure 225: High-resistance generator grounding with a neutral point resistor
There are some alternatives for connection of the neutral point resistor as shown in figure
(low voltage neutral point resistor connected via a DT).
422