ABB RELION 670 Series Technical Manual page 1272

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 21
Basic IED functions
21.9.4
Settings
Table 985: SMAI1 Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
DFTRefExtOut
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType
Ph-N
Ph-Ph
AnalogInputType
Voltage
Current
Table 986: SMAI1 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
1266
DFTRefExtOut and DFTReference shall be set to default value
Settings
InternalDFTRef if no VT inputs are available. Internal nominal frequency DFT
reference is then the reference.
Unit
Step
-
1
-
-
-
-
-
-
-
-
Unit
Step
-
-
%
1
Default
Description
1
Selection of one of the Global Base Value
groups
InternalDFTRef
DFT reference for external output
InternalDFTRef
DFT reference
Ph-N
Input connection type
Voltage
Analog input signal type
Default
Description
Disabled
Negation
10
Limit for frequency calculation in % of
VBase
1MRK 502 066-UUS B
SEMOD55783-1 v2
SEMOD130357-4 v3
PID-3405-SETTINGS v4
Technical manual