ABB RELION 670 Series Technical Manual page 758

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
Table 443: SESRSYN (25) Non group settings (basic)
Name
Values (Range)
SelPhaseBus1
Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
GblBaseSelBus
1 - 12
GblBaseSelLine
1 - 12
SelPhaseBus2
Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
SelPhaseLine1
Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
SelPhaseLine2
Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
CBConfig
No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
Table 444: SESRSYN (25) Non group settings (advanced)
Name
Values (Range)
PhaseShift
-180 - 180
752
Unit
Step
Default
-
-
Phase A
-
1
1
-
1
1
-
-
Phase A
-
-
Phase A
-
-
Phase A
-
-
No voltage sel.
Unit
Step
Default
Deg
1
0
1MRK 502 066-UUS B
Description
Select phase for busbar1
Selection of one of the Global Base Value
groups, Bus
Selection of one of the Global Base Value
groups, Line
Select phase for busbar2
Select phase for line1
Select phase for line2
Select CB configuration
Description
Additional phase angle for selected line
voltage
Technical manual