ABB RELION 670 Series Technical Manual page 1094

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
This method of checking the analog trigger conditions gives a function which is insensitive to DC
offset in the signal. The trip time for this initiation is typically in the range of one cycle, 16 2/3 ms
for a 60 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.
Post Retrigger
Disturbance report function does not automatically respond to any new trig condition during a
recording, after all signals set as trigger signals have been reset. However, under certain
circumstances the fault condition may reoccur during the post-fault recording, for instance by
automatic reclosing to a still faulty power line.
In order to capture the new disturbance it is possible to allow retriggering (
during the post-fault time. In this case a new, complete recording will pickup and, during a period,
run in parallel with the initial recording.
When the retrig parameter is disabled (
until the post-fault (
the post-fault period and lasts longer than the proceeding recording a new complete recording
will be started.
Disturbance report function can handle maximum 3 simultaneous disturbance recordings.
16.6.8
Technical data
Table 782: DRPRDRE technical data
Function
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the Trip Value
recorder per recording
Maximum number of indications in a disturbance
report
Maximum number of events in the Event recording per
recording
Maximum number of events in the Sequence of events
Maximum total recording time (3.4 s recording time
and maximum number of channels, typical value)
Sampling rate
Recording bandwidth
1088
PostRetrig = Disabled ), a new recording will not pickup
PostFaultrecT or TimeLimit ) period is terminated. If a new trig occurs during
Range or value
(0.05–9.90) s
(0.1–10.0) s
(0.5–10.0) s
100, first in - first out
1 ms
30 + 10 (external + internally
derived)
128
30
96
150
1000, first in - first out
340 seconds (100 recordings)
at 50 Hz, 280 seconds (80
recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
1MRK 502 066-UUS B
M12155-173 v6
PostRetrig = Enabled )
M12760-1 v9.1.1
Accuracy
-
-
-
-
See table
968
-
-
-
-
-
-
-
-
-
Technical manual