ABB RELION 670 Series Technical Manual page 595

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Name
Values (Range)
VrLV
10.0 - 3000.0
VrHV
0.10 - 100.00
PhAngleShift
-180 - 180
8.18.6
Monitored data
Table 330: GRPTTR (49R) Monitored data
Name
IMEAS
IDC
THETA
RIPPLVAL
8.18.7
Operation principle
The rotor overload protection GRPTTR (49R) can be illustrated in five separate sub-blocks, see
Figure316.
Technical manual
Unit
Step
V
0.1
kV
0.01
Deg
30
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
Default
Description
400.0
Excitation transformer LV winding rated
Ph-Ph voltage in V
11.00
Excitation transformer HV winding rated
Ph-Ph voltage in kV
30
Phase angle shift across excitation
transformer (degrees)
Unit
Description
A
Measured current, used for calculation of
operate time
A
Average DC current value, used for alarm
and trip logic
%
Overload in percent of set trip level (i.e.
Trip=100%)
%
DC ripple as percent of measured DC
current
Section 8
Current protection
PID-3718-MONITOREDDATA v4
GUID-53D647AD-11D3-4483-89AE-C0325D6C511E v3