Section 16
Monitoring
16.1.5
Settings
The available setting parameters of the measurement function (MMXU, MSQI) are depending on
the actual hardware (TRM) and the logic configuration made in PCM600.
These six functions are not handled as a group, so parameter settings are only available in the first
setting group.
The following terms are used in the Unit and Description columns:
VBase: Base voltage in primary kV. This voltage is used as reference for voltage setting. It can
be suitable to set this parameter to the rated primary voltage supervised object.
IBase: Base current in primary A. This current is used as reference for current setting. It can be
suitable to set this parameter to the rated primary current of the supervised object.
SBase: Base setting for power values in MVA.
Table 732: CVMMXN Non group settings (basic)
Name
Values (Range)
SLowLim
0.0 - 2000.0
SLowLowLim
0.0 - 2000.0
SMin
0.0 - 2000.0
SMax
0.0 - 2000.0
SRepTyp
Cyclic
Dead band
Int deadband
PMin
-2000.0 - 2000.0
PMax
-2000.0 - 2000.0
PRepTyp
Cyclic
Dead band
Int deadband
QMin
-2000.0 - 2000.0
QMax
-2000.0 - 2000.0
QRepTyp
Cyclic
Dead band
Int deadband
PFMin
-1.000 - 1.000
PFMax
-1.000 - 1.000
PFRepTyp
Cyclic
Dead band
Int deadband
VMin
0.0 - 200.0
VMax
0.0 - 200.0
VRepTyp
Cyclic
Dead band
Int deadband
IMin
0.0 - 500.0
Table continues on next page
1016
Unit
Step
Default
%SB
0.1
80.0
%SB
0.1
60.0
%SB
0.1
50.0
%SB
0.1
200.0
-
-
Cyclic
%SB
0.1
-200.0
%SB
0.1
200.0
-
-
Cyclic
%SB
0.1
-200.0
%SB
0.1
200.0
-
-
Cyclic
-
0.001
-1.000
-
0.001
1.000
-
-
Cyclic
%VB
0.1
50.0
%VB
0.1
200.0
-
-
Cyclic
%IB
0.1
5.0
1MRK 502 066-UUS B
Description
Low limit in % of SBase
Low Low limit in % of SBase
Minimum value in % of SBase
Maximum value in % of SBase
Reporting type
Minimum value in % of SBase
Maximum value in % of SBase
Reporting type
Minimum value in % of SBase
Maximum value in % of SBase
Reporting type
Minimum value
Maximum value
Reporting type
Minimum value in % of VBase
Maximum value in % of VBase
Reporting type
Minimum value in % of IBase
Technical manual