1MRK 502 066-UUS B
16.7.6
Operation principle
The Logical signal status report (BINSTATREP) function has 16 inputs and 16 outputs. The output
status follows the inputs and can be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 566: BINSTATREP logical diagram
16.8
Measured value expander block RANGE_XP
16.8.1
Identification
Function description
Measured value expander block
16.8.2
Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic
communication I/O functions (MVGAPC) are provided with measurement supervision
functionality. All measured values can be supervised with four settable limits: low-low limit, low
limit, high limit and high-high limit. The measure value expander block (RANGE_XP) has been
introduced to enable translating the integer output signal from the measuring functions to 5
binary signals: below low-low limit, below low limit, normal, above high limit or above high-high
limit. The output signals can be used as conditions in the configurable logic or for alarming
purpose.
Technical manual
t
IEC09000732-1-en.vsd
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3
t
ANSI/IEEE C37.2
device number
-
Section 16
Monitoring
SEMOD52451-1 v2
SEMOD113212-2 v3
SEMOD52450-4 v7