ABB RELION 670 Series Technical Manual page 1054

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
Function
Time delay for oil alarm
Reset time delay for oil alarm
Time delay for oil lockout
Time delay for temperature alarm
Reset time delay for temperature
alarm
Time delay for temperature lockout
16.4
Breaker monitoring SSCBR
16.4.1
Identification
Function description
Breaker monitoring
16.4.2
Functionality
The breaker monitoring function SSCBR is used to monitor different parameters of the breaker
condition. The breaker requires maintenance when the number of operations reaches a predefined
value. For a proper functioning of the circuit breaker, it is essential to monitor the circuit breaker
operation, spring charge indication or breaker wear, travel time, number of operation cycles and
estimate the accumulated energy during arcing periods.
16.4.3
Function block
I3P*
BLOCK
BLKALM
TRIND
POSOPEN
POSCLOSE
PRESALM
PRESLO
SPRCHRST
SPRCHRD
RSTCBWR
RSTTRVT
RSTIPOW
RSTSPCHT
ANSI14000061 V1 EN-US
Figure 543: SSCBR function block
1048
SSCBR
OPENPOS
CLOSEPOS
INVDPOS
TRCMD
TRVTOPAL
TRVTCLAL
OPERALM
OPERLO
CBLIFEAL
MONALM
IPOWALPH
IPOWLOPH
SPCHALM
GPRESALM
GPRESLO
ANSI14000061-1-en.vsd
Range or value
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
SSCBR
-
1MRK 502 066-UUS B
Accuracy
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7
ANSI/IEEE C37.2
device number
-
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v10
GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v11
Technical manual