1MRK 502 066-UUS B
Name
LNGTHERR
CRCERROR
REMCOMF
LOWLEVEL
Table 932: LDCMRecBinStat2 Output signals
Name
CH1
CH2
CH3
CH4
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
Table 933: LDCMRecBinStat3 Output signals
Name
CH1
CH2
CH3
CH4
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
Table continues on next page
Technical manual
Type
Description
BOOLEAN
Wrong length of the incoming message
BOOLEAN
Identified error by CRC check in incoming message
BOOLEAN
Remote terminal indicates problem with received message
BOOLEAN
Low signal level on the receive link
Type
Description
STRING
Remote communication channel 1
STRING
Remote communication channel 2
STRING
Remote communication channel 3
STRING
Remote communication channel 4
BOOLEAN
Detected error in the differential communication
BOOLEAN
Detected error in remote end with incoming message
BOOLEAN
No carrier is detected in the incoming message
BOOLEAN
No start and stop flags identified for the incoming message
BOOLEAN
Incoming message from non-valid address
BOOLEAN
Wrong length of the incoming message
BOOLEAN
Identified error by CRC check in incoming message
BOOLEAN
Transmission time is longer than permitted
BOOLEAN
Error in echo synchronization
BOOLEAN
Remote terminal indicates problem with received message
BOOLEAN
Remote terminal indicates problem with GPS synchronization
BOOLEAN
Link error, values are substituted
BOOLEAN
Low signal level on the receive link
Type
Description
STRING
Remote communication channel 1
STRING
Remote communication channel 2
STRING
Remote communication channel 3
STRING
Remote communication channel 4
BOOLEAN
Detected error in the differential communication
BOOLEAN
Detected error in remote end with incoming message
BOOLEAN
No carrier is detected in the incoming message
BOOLEAN
No start and stop flags identified for the incoming message
BOOLEAN
Incoming message from non-valid address