ABB RELION 670 Series Technical Manual page 1210

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 18
Station communication
Table 920: GOOSESPRCV Output signals
Name
SPOUT
DATAVALID
COMMVALID
TEST
18.14.5
Settings
Table 921: GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
18.14.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
1204
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
-
-
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the binary single point values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
Description
Single point output
Data valid for single point output
Communication valid for single point output
Test output
Default
Description
Disabled
Operation Disabled/Enabled
1MRK 502 066-UUS B
PID-2527-OUTPUTSIGNALS v18
PID-2527-SETTINGS v18
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v2
Technical manual