Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
The voltages (phase or phase-phase voltage, magnitude and angle) are available on the outputs
and each magnitude output has a corresponding supervision level output (Vxy_RANG). The
supervision output signal is an integer in the interval 0-4, see section
16.1.7.5
Voltage and current sequence measurements VMSQI, CMSQI
The measurement functions must be connected to three-phase current (CMSQI) or voltage
(VMSQI) input in the configuration tool to be operable. No outputs, other than X_RANG, are
calculated within the measuring blocks and it is not possible to calibrate the signals. Input signals
are obtained from the pre-processing block and transferred to corresponding output.
Positive, negative and three times zero sequence quantities are available on the outputs (voltage
and current, magnitude and angle). Each magnitude output has a corresponding supervision level
output (X_RANGE). The output signal is an integer in the interval 0-4, see section
supervision".
16.1.8
Technical data
Table 750: CVMMXN technical data
Function
Frequency
Voltage
Current
Active power, P
Reactive power, Q
Apparent power, S
Power factor, cos (φ)
1040
Range or value
(0.95-1.05) x f
n
(10 to 300) V
(0.1-4.0) x I
n
(10 to 300) V
(0.1-4.0) x I
n
(100 to 220) V
(0.5-2.0) x I
n
cos φ> 0.7
(10 to 300) V
(0.1-4.0) x I
n
(100 to 220) V
(0.5-2.0) x I
n
cos φ< 0.7
(10 to 300) V
(0.1-4.0) x I
n
(100 to 220) V
(0.5-2.0) x I
n
(10 to 300) V
(0.1-4.0) x I
n
(100 to 220) V
(0.5-2.0) x I
n
"Measurement
Accuracy
±2.0 mHz
±0.3% of V at V≤ 50 V
±0.2% of V at V> 50 V
±0.8% of I at 0.1 x I
< I < 0.2 x I
n
± 0.5% of I at 0.2 x I
< I < 0.5 x I
n
±0.2% of I at 0.5 x I
< I < 4.0 x I
n
±0.5% of S
at S ≤0.5 x S
n
n
±0.5% of S at S > 0.5 x S
n
±0.2% of P
±0.5% of S
at S ≤0.5 x S
n
n
±0.5% of S at S > 0.5 x S
n
±0.2% of Q
±0.5% of S
at S ≤0.5 x S
n
n
±0.5% of S at S >0.5 x S
n
±0.2% of S
<0.02
<0.01
1MRK 502 066-UUS B
supervision".
SEMOD54417-299 v6
"Measurement
M12386-1 v14.1.1
n
n
n
Technical manual