1MRK 502 066-UUS B
Name
Values (Range)
I1Min
0.0 - 500.0
I1Max
0.0 - 500.0
I1RepTyp
Cyclic
Dead band
Int deadband
I1AngDbRepInt
1 - 300
I1AngMax
-180.000 -
180.000
I1AngRepTyp
Cyclic
Dead band
Int deadband
I2DbRepInt
1 - 300
I2ZeroDb
0 - 100000
I2Min
0.0 - 500.0
I2Max
0.0 - 500.0
I2RepTyp
Cyclic
Dead band
Int deadband
I2LimHys
0.000 - 100.000
I2AngDbRepInt
1 - 300
I2AngMin
-180.000 -
180.000
I2AngRepTyp
Cyclic
Dead band
Int deadband
Table 739: CMSQI Non group settings (advanced)
Name
Values (Range)
3I0HiHiLim
0.0 - 500.0
3I0HiLim
0.0 - 500.0
3I0LowLim
0.0 - 500.0
3I0LowLowLim
0.0 - 500.0
3I0AngZeroDb
0 - 100000
I1HiHiLim
0.0 - 500.0
I1HiLim
0.0 - 500.0
I1LowLim
0.0 - 500.0
I1LowLowLim
0.0 - 500.0
I1LimHys
0.000 - 100.000
I1AngZeroDb
0 - 100000
Table continues on next page
Technical manual
Unit
Step
Default
%IB
0.1
50.0
%IB
0.1
200.0
-
-
Cyclic
Type
1
10
Deg
0.001
180.000
-
-
Cyclic
Type
1
10
m%
1
1
%IB
0.1
50.0
%IB
0.1
200.0
-
-
Cyclic
%
0.001
5.000
Type
1
10
Deg
0.001
-180.000
-
-
Cyclic
Unit
Step
Default
%IB
0.1
150.0
%IB
0.1
120.0
%IB
0.1
80.0
%IB
0.1
60.0
m%
1
0
%IB
0.1
150.0
%IB
0.1
120.0
%IB
0.1
80.0
%IB
0.1
60.0
%
0.001
5.000
m%
1
0
Description
Minimum value in % of IBase
Maximum value in % of IBase
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
Minimum value in % of IBase
Maximum value in % of IBase
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Minimum value
Reporting type
Description
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Zero point clamping in 0.001% of range
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0.001% of range
Section 16
Monitoring
1023