ABB RELION 670 Series Technical Manual page 1368

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 23
Injection equipment hardware
23.1.2
Injection unit REX060 from rear side
23.1.2.1
Injection unit REX060
IED and
Injection
connectors
IEC11000018 V1 EN-US
Figure 694: Rear and top view of injection unit REX060
23.2
Injection unit REX060
23.2.1
Introduction
The injection unit REX060 is used to inject voltage and current signals to the generator or motor
stator and rotor circuits. REX060 generates two square wave signals with different frequencies for
injection into the stator and rotor circuits respectively. The response from the injected voltage
and currents are then measured by the REX060 unit and amplified to a level suitable for the analog
voltage inputs of IED.
23.2.2
Design
REX060 consists of a standard enclosure (6U, 1/2 x 19"). In this enclosure, the modules for stator
(SIM) and/or rotor (RIM) earth fault protection are installed. The stator injection transformer and
the power supply are also installed inside the enclosure.
On the front of the enclosure there is a backlit LCD, control buttons and a key switch.
In figure
module. Row 1 contains mains frequency information. Row 2-3 contains stator information and
row 4-5 rotor. Column 1 (empty) gives status, column 2 and 3 are informative and column 4
contains variables, settable by the keypad.
1362
Power
Top view
connector
BackPlane
Front-plate
HMI and Logic
IEC11000018-1-en.vsd
695
below the content of display is shown for a REX060 with one SIM and one RIM
Back view
X11
X61
X81
1
1
1
5
18
18
X62
X82
1
1
5
5
1MRK 502 066-UUS B
GUID-9987BF42-9133-4606-9ABB-0C918EBE8AE3 v1
Front view
Injection switch
GUID-59174783-57D0-4F39-AE7F-B59FA88CB230 v1
GUID-EC628DB7-CEF0-4700-9F8E-27B9934549EA v2
Technical manual