ABB RELION 670 Series Technical Manual page 956

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 15
Logic
Name
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
Table 596: ALMCALH Output signals
Name
ALARM
15.3.5
Settings
Table 597: ALMCALH Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
15.3.6
Operation principle
The logic for group alarm ALMCALH block is provided with 16 input signals and one ALARM output
signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output ALARM signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM output signal
will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.
Input 1
ANSI13000191 V1 EN-US
Figure 490: Group alarm logic
950
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Type
BOOLEAN
Unit
Step
-
-
1
Description
Binary input 9
Binary input 10
Binary input 11
Binary input 12
Binary input 13
Binary input 14
Binary input 15
Binary input 16
Description
OR function betweeen inputs 1 to 16
Default
Description
Disabled
Operation Disabled/Enabled
200 ms
0
1MRK 502 066-UUS B
PID-4126-OUTPUTSIGNALS v3
PID-4126-SETTINGS v3
GUID-0405BB7B-7EF7-4546-92CD-F703AA0DD9F4 v2
ALARM
ANSI13000191-1-en.vsd
Technical manual