The Under-Time logic always uses the pickup signal from the step 4. The Under-Time logic will
normally be set to operate for a lower current level than the SOTF function. The Under-Time logic
can also be blocked by the 2
power transformer inrush currents can occur at breaker closing. This logic is typically used to
detect asymmetry of CB poles immediately after switching of the circuit breaker. The Under-Time
logic is activated either from change in circuit breaker position or from circuit breaker close and
open command pulses. This selection is done by setting parameter
pickup from step 4 this logic will give a trip after a set delay
to a relatively short time (default 300 ms). Practically the Under-Time logic acts as circuit breaker
pole-discrepancy protection, but it is only active immediately after breaker switching. The Under-
Time logic can only be used in solidly or low impedance grounded systems.
SOTF
BLOCK
UNDERTIME
Open
Close
Close command
ANSI06000643 V6 EN-US
Figure 258: Simplified logic diagram for SOTF and Under-Time features
EF4PTOC (51N/67N) Logic Diagram Simplified logic diagram for the complete EF4PTOC (51N/67N)
function is shown in figure 259:
Technical manual
nd
harmonic restraint feature. This enables high sensitivity even if
200 ms
Open
t
200 ms
Closed
ActivationSOTF
t
Close command
STIN2
StepForSOTF
STIN3
2nd Harmonic
HarmResSOFT
OR
ActUnderTime
STIN4
t4U
tSOTF
AND
t
AND
tUnderTime
AND
t
t4U
AND
ActUnderTime . In case of a
tUnderTime . This delay is normally set
SOTF
OFF
SOTF
TRIP
UnderTime
SOTF or
UnderTime
OR
ANSI06000643-6-en.vsdx
Section 8
Current protection
M13941-3 v4
489