ABB RELION 670 Series Technical Manual page 1032

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
Name
Values (Range)
V1AngRepTyp
Cyclic
Dead band
Int deadband
V2HiHiLim
0.0 - 200.0
V2HiLim
0.0 - 200.0
V2LowLim
0.0 - 200.0
V2LowLowLim
0.0 - 200.0
V2AngZeroDb
0 - 100000
Table 742: VNMMXU Non group settings (basic)
Name
Values (Range)
VA_DbRepInt
1 - 300
Operation
Disabled
Enabled
VA_ZeroDb
0 - 100000
VA_Max
0.0 - 200.0
VA_RepTyp
Cyclic
Dead band
Int deadband
GlobalBaseSel
1 - 12
VA_LimHys
0.000 - 100.000
VA_AnDbRepInt
1 - 300
VB_DbRepInt
1 - 300
VB_ZeroDb
0 - 100000
VB_Max
0.0 - 200.0
VB_RepTyp
Cyclic
Dead band
Int deadband
VB_LimHys
0.000 - 100.000
VB_AnDbRepInt
1 - 300
VC_DbRepInt
1 - 300
VC_ZeroDb
0 - 100000
VC_Max
0.0 - 200.0
Table continues on next page
1026
Unit
Step
Default
-
-
Cyclic
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
m%
1
0
Unit
Step
Default
Type
1
10
-
-
Disabled
m%
1
1
%VB
0.1
200.0
-
-
Cyclic
-
1
1
%
0.001
5.000
Type
1
10
Type
1
10
m%
1
1
%VB
0.1
200.0
-
-
Cyclic
%
0.001
5.000
Type
1
10
Type
1
10
m%
1
1
%VB
0.1
200.0
1MRK 502 066-UUS B
Description
Reporting type
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Zero point clamping in 0.001% of range
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Disbled/Enabled operation
Zero point clamping
Maximum value in % of VBase
Reporting type
Selection of one of the Global Base Value
groups
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
Maximum value in % of VBase
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
Maximum value in % of VBase
Technical manual
PID-3756-SETTINGS v5

Advertisement

Table of Contents
loading

This manual is also suitable for: