1MRK 502 066-UUS B
23.1.1.4
Shunt resistor unit REX062
IEC11000038 V1 EN-US
Figure 692: Shunt resistor unit REX062
Ø 5,5 [0,22]
IEC11000039 V2 EN-US
Figure 693: REX062 measures and drilling plan
REX062 shall be mounted close to the IED. It is recommended that REX060 and REX062 are
mounted in the same cubicle as the IED.
Technical manual
217 [8,54]
84 [3,3]
84 [3,3]
The surface of REX062 unit may be temporarily very hot due to heat dissipation, up
to about 65° C above the ambient temperature. It must be installed to get a open
air convection and prevent contact with combustible material to the surface.
X1
IEC11000038-1-en.vsd
155 [6,1]
2 [0,079]
Section 23
Injection equipment hardware
GUID-184D9033-33F3-4F85-8847-E9FDC95C3C41 v5
IEC11000039-2-en.vsd
1361