ABB RELION 670 Series Technical Manual page 1025

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Name
Values (Range)
FrLowLowLim
0.000 - 100.000
FrLimHyst
0.000 - 100.000
VGenZeroDb
1 - 100
IGenZeroDb
1 - 100
VMagComp5
-10.000 - 10.000
VMagComp30
-10.000 - 10.000
VMagComp100
-10.000 - 10.000
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IMagComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
Table 734: CMMXU Non group settings (basic)
Name
Values (Range)
IA_DbRepInt
1 - 300
Operation
Disabled
Enabled
IA_Max
0.0 - 500.0
IA_RepTyp
Cyclic
Dead band
Int deadband
GlobalBaseSel
1 - 12
IA_AngDbRepInt
1 - 300
IB_DbRepInt
1 - 300
IB_Max
0.0 - 500.0
IB_RepTyp
Cyclic
Dead band
Int deadband
IB_AngDbRepInt
1 - 300
IC_DbRepInt
1 - 300
Table continues on next page
Technical manual
Unit
Step
Default
Hz
0.001
45.000
%
0.001
5.000
%VB
1
5
%IB
1
5
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
Unit
Step
Default
Type
1
10
-
-
Disabled
%IB
0.1
200.0
-
-
Cyclic
-
1
1
Type
1
10
Type
1
10
%IB
0.1
200.0
-
-
Cyclic
Type
1
10
Type
1
10
Description
Low Low limit (physical value)
Hysteresis value in % of range (common
for all limits)
Zero point clamping in % of UBase
Zero point clamping in % of IBase
Magnitude factor to calibrate voltage at
5% of Vn
Magnitude factor to calibrate voltage at
30% of Vn
Magnitude factor to calibrate voltage at
100% of Vn
Magnitude factor to calibrate current at
5% of In
Magnitude factor to calibrate current at
30% of In
Magnitude factor to calibrate current at
100% of In
Angle calibration for current at 5% of In
Angle calibration for current at 30% of In
Angle calibration for current at 100% of In
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Disbled/Enabled operation
Maximum value in % of IBase
Reporting type
Selection of one of the Global Base Value
groups
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Maximum value in % of IBase
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Section 16
Monitoring
PID-3760-SETTINGS v6