Section 20
Security
Name of signal
TIMESYNCHERROR
RTEERROR
IEC61850ERROR
DNP3
LMDERROR
APPERROR
SETCHGD
SETGRPCHGD
Table 950: Self-supervision's hardware dependent internal signals
Card
PSM
BIM
BOM
IOM
MIM
SOM
NUM
Table continues on next page
1230
Description
Time
Synchronizat
ion status
Runtime
Execution
Error status
IEC 61850
Error status
DNP3 error
status
LON/Mip
Device Error
status
Runtime
Application
Error status
Settings
changed
Setting
groups
changed
Name of signal
Description
PSM-Error
Power
Supply
Module Error
status
BIM-Error
Binary In
Module Error
status
BOM-Error
Binary Out
Module Error
status
IOM-Error
In/Out
Module Error
status
MIM-Error
Millampere
Input Module
Error status
SOM-Error
Static Out
Module Error
status
NUM-Error
Numerical/C
PU Module
Error status
Displayed on
Reasons for activation
local HMI as
Time synch
This signal will be active when the source of the time
synchronization is lost, or when the time system has to
make a time reset.
Runtime
This signal will be active if the Runtime Engine failed to
execution
do some actions with the application threads. The
actions can be loading of settings or parameters for
components, changing of setting groups, loading or
unloading of application threads.
IEC61850
This signal will be active if the IEC 61850 stack did not
succeed in some actions like reading IEC 61850
configuration, startup, for example
DNP3
This signal will be active when DNP3 detects any
configuration error during startup.
SLM301
LON network interface, MIP/DPS, is in an unrecoverable
error state.
Runtime App
This signal will be active if one or more of the application
Error
threads are not in the state that Runtime Engine expects.
The states can be CREATED, INITIALIZED, RUNNING, for
example
Settings
This signal will generate an Internal Event to the Internal
changed
Event list if any settings are changed.
Settings
This signal will generate an Internal Event to the Internal
changed
Event list if any setting groups are changed.
Displayed on
Reasons for activation
local HMI as
PSM1
Activated if the module has a hardware error.
BIMn
Activated if the module has a hardware error.
n = slot number
BOMn
Activated if the module has a hardware error.
n = slot number
IOMn
Activated if the module has a hardware error.
n = slot number
MIMn
Activated if the module has a hardware error.
n = slot number
SOMn
Activated if the module has a hardware error.
n = slot number
NUM30
Activated if the module has a hardware or
software error.
1MRK 502 066-UUS B