Section 15
Logic
15.15.6.1
Operation accuracy
The accuracy of TEIGAPC depends on essentially three factors
function cycle time
the pulse length
the number of pulses, that is, the number of rising and falling flank pairs
In principle, a shorter function cycle time, longer integrated time length or more pulses may lead
to reduced accuracy.
15.15.6.2
Memory storage
The value of the integrated elapsed time is retained in a non-volatile memory.
15.15.7
Technical data
Table 710: TEIGAPC Technical data
Elapsed time integration
Table 711: Number of TEIGAPC instances
Function
TEIGAPC
15.16
Comparator for integer inputs - INTCOMP
15.16.1
Identification
Function description
Comparison of integer values
15.16.2
Functionality
The function gives the possibility to monitor the level of integer values in the system relative to
each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.
1002
Function
Cycle time (ms)
3
8
100
3 ms
4
Range or value
0 ~ 999999.9 s
0 ~ 999999.9 s
0 ~ 999999.9 s
Quantity with cycle time
8 ms
4
IEC 61850
IEC 60617
identification
identification
INTCOMP
Int<=>
1MRK 502 066-UUS B
GUID-E0772193-9F6E-43DA-B642-2923565E5D4C v3
GUID-6FDD6590-30F9-4CC1-AC9D-945544AB8688 v3
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Accuracy
±0.2% or ±20 ms whichever
is greater
±0.2% or ±100 ms whichever
is greater
±0.2% or ±250 ms whichever
is greater
100 ms
4
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
ANSI/IEEE C37.2
device number
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1