ABB RELION 670 Series Technical Manual page 1165

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
time tagged in the main processing module, while the binary input channels are time tagged
directly on each I/O module. The events are produced according to the set of event masks. The
event masks are treated commonly for both the LON and SPA channels. All events according to the
event mask are stored in a buffer, which contains up to 1000 events. If new events appear before
the oldest event in the buffer is read, the oldest event is overwritten and an overflow alarm
appears.
Two special signals for event registration purposes are available in the IED, Terminal Restarted
(0E50) and Event buffer overflow (0E51).
The input parameters can be set individually from the Parameter Setting Tool (PST) under: Main
Menu/Settings / IED Settings / Monitoring / Event Function or via parameter Setting Tool (PST)
as follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for integers
has no semantic, prefer to be set by the user)
The Status and event codes for the Event functions are found in table 858.
Table 858: Status and event codes
Event block
EVENT:1
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
EVENT:2
EVENT:3
-
-
-
EVENT:20
These values are only applicable if the Event mask is masked ≠ OFF.
Technical manual
Single indication
Status
Set event
Reset
event
22O1
22E33
22E32
22O2
22E35
22E34
22O3
22E37
22E36
22O4
22E39
22E38
22O5
22E41
22E40
22O6
22E43
22E42
22O7
22E45
22E44
22O8
22E47
22E46
22O9
22E49
22E48
22O10
22E51
22E50
22O11
22E53
22E52
22O12
22E55
22E54
22O13
22E57
22E56
22O14
22E59
22E58
22O15
22E61
22E60
22O16
22E63
22E62
230..
23E..
23E..
240..
24E..
24E..
-
-
-
-
-
-
-
-
-
410..
41E..
41E..
1)
Double indication
Intermed
Closed
iate 00
10
22E0
22E1
22E4
22E5
22E8
22E9
22E12
22E13
22E16
22E17
22E20
22E21
22E24
22E25
22E28
22E29
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
23E..
23E..
24E..
23E..
-
-
-
-
-
-
41E..
41E..
Station communication
Open
Undefined
01
11
22E2
22E3
22E6
22E7
22E10
22E11
22E14
22E15
22E18
22E19
22E22
22E23
22E26
22E27
22E30
22E31
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
23E..
23E..
24E..
24E..
-
-
-
-
-
-
41E..
41E..
Section 18
1159

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670

Table of Contents