Section 23
Injection equipment hardware
23.5.2
Type tests according to standards
Table
1069:
Test
1 MHz Oscillatory burst disturbance
100 kHz slow damped oscillatory wave
immunity test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance test
Surge immunity test
Power frequency immunity test
Power frequency magnetic field test
Radiated electromagnetic field disturbance
test
Radiated electromagnetic field disturbance
test
Conducted electromagnetic field disturbance
test
Voltage dips and short interruptions
Radiated emission
Conducted emission
Table
1070:
Test
Dielectric test
Impulse voltage test
Insulation resistance
1370
Electromagnetic compatibility tests
Insulation tests, REX060, REX062 and REG670
Type test values
2.5 kV
2.5 kV
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
1-2 kV, and 2-4 kV, 1.2/50
µs
High energy
150-300 V
1000 A/m, 3 s
100 A/m, cont.
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m, 80-1000 MHz
10 V, 0.15-80 MHz
Dips:
40% /200 ms
70% /500 ms
Interruptions:
0-50 ms: No restart
0... ∞ s: Correct behaviour
at power down
30-1000 MHz
0.15-30 MHz
Type test values
2.0 kV AC, 1 min
5.0 kV, 1.2/50 µs, 0.5 J
>100 MΩ at 500V DC
1MRK 502 066-UUS B
GUID-87197CB5-8590-4872-A5B6-8C6D2A815C9E v4
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.3
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-8
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEC 60255-26
IEC 60255-26
Reference standard
IEC 60255-27
IEC 60255-27
IEC 60255-27