The TEST output will go HIGH if the sending IED is in test mode.
18.14
GOOSE function block to receive a single point value
GOOSESPRCV
18.14.1
Identification
Function description
GOOSE function block to receive a
single point value
18.14.2
Functionality
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via GOOSE.
18.14.3
Function block
BLOCK
IEC10000248 V1 EN-US
Figure 613: GOOSESPRCV function block
18.14.4
Signals
Table 919: GOOSESPRCV Input signals
Name
BLOCK
Technical manual
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the measured value.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
GOOSESPRCV
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
Type
BOOLEAN
IEC 61850
IEC 60617
identification
identification
GOOSESPRCV
-
Default
Description
0
Block of function
Station communication
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
ANSI/IEEE C37.2
device number
-
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v2
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
PID-2527-INPUTSIGNALS v18