1MRK 502 066-UUS B
Table 987: SMAI2 Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType
Ph-N
Ph-Ph
AnalogInputType
Voltage
Current
Table 988: SMAI2 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
21.9.5
Operation principle
Every Signal matrix for analog inputs function (SMAI) can receive four analog signals (three phases
and one neutral or residual value), either voltage or current, see figure
outputs give information about every aspect of the 3ph analog signals acquired (phase angle, RMS
value, frequency and frequency derivates etc. – 244 values in total). The BLOCK input will force all
outputs to value zero if BLOCK is TRUE (1). However, when the disturbance recorder is connected
to the single-phase outputs of SMAI, the sample data to the disturbance recorder will not be
blocked. The disturbance recorder bypasses SMAI to the sample data channels.
System phase rotation and frequency are defined using the
in the primary system values PRIMVAL function. Logic 1 in the REVROT input to the SMAI function
means that the phase rotation is changed relative to the set
The output signal AI1 to AI4 are direct output of the, in SMT, connected input to GRPx_A, GRPxB,
GRPxC and GRPx_N, x=1-12. AIN is always calculated residual sum from the first three inputs. A3P is
grouped, three-phase information containing all relevant information about four connected
inputs. Note that all other functions, with a few exceptions, use this output in configuration. Note
Technical manual
Unit
Step
Default
-
1
1
-
-
InternalDFTRef
-
-
Ph-N
-
-
Voltage
Unit
Step
Default
-
-
Disabled
%
1
10
Description
Selection of one of the Global Base Value
groups
DFT reference
Input connection type
Analog input signal type
Description
Negation
Limit for frequency calculation in % of
VBase
638
and figure 639. SMAI
PhaseRotation and Frequency settings
PhaseRotation in PRIMVAL.