Section 16
Monitoring
16.9.6
Settings
Table 791: L4UFCNT Group settings (basic)
Name
Values (Range)
Operation
Disabled
On
CountType
Positive edge
Negative edge
Both edges
CounterLimit1
1 - 65535
CounterLimit2
1 - 65535
CounterLimit3
1 - 65535
CounterLimit4
1 - 65535
MaxValue
1 - 65535
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
InitialValue
0 - 65535
16.9.7
Monitored data
Table 792: L4UFCNT Monitored data
Name
VALUE
16.9.8
Technical data
Table 793: L4UFCNTtechnical data
Function
Counter value
Max. count up speed
16.10
Running hour-meter TEILGAPC
16.10.1
Identification
Function Description
Running hour-meter
1096
Unit
Step
-
-
-
-
-
1
-
1
-
1
-
1
-
1
-
-
-
1
Type
Values (Range)
INTEGER
-
Range or value
0-65535
30 pulses/s (50% duty cycle)
IEC 61850
identification
TEILGAPC
Default
Description
Disabled
Operation Disabled/Enabled
Positive edge
Select counting on positive and/or
negative sides
100
Value of the first limit
200
Value of the second limit
300
Value of the third limit
400
Value of the fourth limit
500
Maximum count value
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
0
Initial count value after reset of the
function
Unit
Description
-
Counted value
Accuracy
-
-
IEC 60617
ANSI/IEEE C37.2 device
identification
number
-
-
1MRK 502 066-UUS B
PID-3553-SETTINGS v5
PID-3553-MONITOREDDATA v4
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Technical manual