ABB RELION 670 Series Technical Manual page 1234

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 20
Security
20.5.3
Signals
Table 948: INTERRSIG Output signals
Name
FAIL
WARNING
TSYNCERR
RTCERR
DISABLE
20.5.4
Settings
The function does not have any parameters available in the local HMI or PCM600.
20.5.5
Operation principle
The self-supervision operates continuously and includes:
Normal micro-processor watchdog function.
Checking of digitized measuring signals.
Other alarms, for example hardware and time synchronization.
The self-supervision function status can be monitored from the local HMI or from the Event Viewer
in PCM600.
Under the Diagnostics menu in the local HMI, the actual information from the self-supervision
function can be reviewed. The information can be found under Main menu/Diagnostics/Internal
events or Main menu/Diagnostics/IED status/General. The information from the self-supervision
function is also available in the Event Viewer in PCM600.
IEC15000414 V1 EN-US
Figure 623: IED general status in local HM
The self supervision records internal signal changes in an internal event list. A maximum of 40
internal events are stored in a first-in, first-out manner.
1228
Type
Description
BOOLEAN
Internal fail
BOOLEAN
Internal warning
BOOLEAN
Time synchronization error
BOOLEAN
Real time clock error
BOOLEAN
Application Disable
IEC15000414-1-en.vsdx
1MRK 502 066-UUS B
IP9674-1 v2
PID-4077-OUTPUTSIGNALS v5
ABBD8E15533 v3
IP11943-1 v2
M11401-3 v11
Technical manual