ABB RELION 670 Series Technical Manual page 1311

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Name
BO10VALUE
BO10FORCE
BO10
BO11VALUE
BO11FORCE
BO11
BO12VALUE
BO12FORCE
BO12
22.2.9.6
Technical data
Table
1020:
Function of quantity
Rated voltage
Number of outputs
Impedance open state
Test voltage across open contact, 1
min
Current carrying capacity:
Continuous
1.0 s
Making capacity at capacitive load with
the maximum capacitance of 0.2 μF :
0.2 s
1.0 s
Breaking capacity for DC with L/R ≤ 40
ms
Table continues on next page
Technical manual
Type
Values (Range)
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Unit
1=1
-
0=0
0=Normal
-
1=Forced
0=Normal
-
1=Forced
2=Blocked
1=1
-
0=0
0=Normal
-
1=Forced
0=Normal
-
1=Forced
2=Blocked
1=1
-
0=0
0=Normal
-
1=Forced
0=Normal
-
1=Forced
2=Blocked
Static binary output trip
48-60 VDC
6
~300 kΩ
No galvanic separation
5 A
10 A
30 A
10 A
48 V/1 A
60 V/0.75 A
Description
Binary output 10 value
Binary output 10 force
Binary output 10 status
Binary output 11 value
Binary output 11 force
Binary output 11 status
Binary output 12 value
Binary output 12 force
Binary output 12 status
110-250 VDC
6
~810 kΩ
No galvanic separation
5 A
10 A
30 A
10 A
110 V/0.4 A
125 V/0.35 A
Section 22
IED hardware
SEMOD175396-1 v1
SEMOD175395-2 v9
1305