ABB RELION 670 Series Technical Manual page 734

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 13
Secondary system supervision
13.1.4
Signals
Table 421: CCSSPVC (87) Input signals
Name
I3P
IREF
BLOCK
Table 422: CCSSPVC (87) Output signals
Name
FAIL
ALARM
13.1.5
Settings
Table 423: CCSSPVC (87) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IMinOp
10 - 200
Table 424: CCSSPVC (87) Group settings (advanced)
Name
Values (Range)
Pickup_Block
20 - 500
Table 425: CCSSPVC (87) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
13.1.6
Operation principle
Current circuit supervision CCSSPVC (87) compares the absolute value of the vectorial sum of the
three phase currents |ΣIphase| and the numerical value of the residual current |Iref| from another
current transformer set, see figure 388.
728
Type
Default
Description
GROUP
-
Group signal for three phase current input
SIGNAL
GROUP
-
Residual reference current input
SIGNAL
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Detection of current circuit failure
BOOLEAN
Alarm for current circuit failure
Unit
Step
-
-
%IB
1
Unit
Step
%IB
1
Unit
Step
-
1
Default
Description
Disabled
Operation Disabled/Enabled
20
Minimum operate current differential
pickup in % of IBase
Default
Description
150
Block of the function at high phase
current, in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 502 066-UUS B
PID-3482-INPUTSIGNALS v6
PID-3482-OUTPUTSIGNALS v6
PID-3482-SETTINGS v6
M12396-5 v9
Technical manual