18.15
GOOSE VCTR configuration for send and receive
GOOSEVCTRCONF
18.15.1
Identification
18.15.2
Settings
18.16
GOOSE voltage control receiving block GOOSEVCTRRCV
18.16.1
Identification
18.16.2
Signals
18.17
MULTICMDRCV and MULTICMDSND
Function description
Multiple command and receive
Multiple command and send
18.17.1
Functionality
The IED provides two function blocks enabling several IEDs to send and receive signals via the
interbay bus. The sending function block, MULTICMDSND, takes 16 binary inputs. LON enables
these to be transmitted to the equivalent receiving function block, MULTICMDRCV, which has 16
binary outputs.
18.17.2
Design
18.17.2.1
General
The common behavior for all 16 outputs of the MULTICMDRCV is set to either of two modes:
Steady or Pulse.
1 = Steady: This mode simply forwards the received signals to the binary outputs.
2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse with a duration of
exactly one execution cycle is triggered on the corresponding binary output. This means that
no connected function block may have a cycle time that is higher than the execution cycle time
of the particular MULTICMDRCV instance.
Technical manual
IEC 61850
IEC 60617
identification
identification
MULTICMDRCV
-
MULTICMDSND
-
Station communication
GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v2
ANSI/IEEE C37.2
device number
-
-
Section 18
SEMOD119881-1 v3
M14790-3 v5
SEMOD119958-1 v1
M14792-3 v3