Section 10
Frequency protection
10.1.4
Signals
Table 380: SAPTUF (81L) Input signals
Name
V3P
BLOCK
BLKTRIP
BLKREST
Table 381: SAPTUF (81L) Output signals
Name
TRIP
PICKUP
RESTORE
BLKDMAGN
FREQ
10.1.5
Settings
Table 382: SAPTUF (81L) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFrequency
35.00 - 75.00
tDelay
0.000 - 60.000
tReset
0.000 - 60.000
tRestore
0.000 - 60.000
RestoreFreq
45.00 - 65.00
TimerMode
Definite timer
Volt based timer
VNom
50.0 - 150.0
VMin
50.0 - 150.0
Exponent
0.0 - 5.0
t_MaxTripDelay
0.010 - 60.000
t_MinTripDelay
0.010 - 60.000
666
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Blocking operate output
BOOLEAN
0
Blocking restore output
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Common pickup signal
BOOLEAN
Restore signal for load restoring purposes
BOOLEAN
Measurement blocked due to low voltage amplitude
REAL
Measured frequency
Unit
Step
-
-
Hz
0.01
s
0.001
s
0.001
s
0.001
Hz
0.01
-
-
%VB
1.0
%VB
1.0
-
0.1
s
0.001
s
0.001
Default
Description
Disabled
Operation Disabled/Enabled
48.80
Frequency set value
0.200
Operate time delay
0.000
Time delay for reset
0.000
Restore time delay
50.10
Restore frequency value
Definite timer
Setting for choosing timer mode
100.0
Nominal voltage for voltage based timer in
% of UBase
90.0
Lower operation limit for voltage based
timer in % of VBase
1.0
For calculation of the curve form for
voltage based timer
1.000
Maximum time operation limit for voltage
based timer
1.000
Minimum time operation limit for voltage
based timer
1MRK 502 066-UUS B
PID-3901-INPUTSIGNALS v6
PID-3901-OUTPUTSIGNALS v6
PID-3901-SETTINGS v6