Section 18
Station communication
intermediate and faulty states may be suppressed by setting the
Off . See the settings for RS485 and optical serial communication for more information.
Input SELECT is a single-indication signal, and it is also GI enabled. State transitions to ON and
OFF are reported spontaneously.
When input BLOCK is ON, the function will ignore GI requests and cease all monitoring activity.
Consequently, no transitions will be detected.
The I103POSCMD function is also equipped with three additional commands: Select, Operate and
Cancel. These are hidden in ACT and respond only to the base INF+1, INF+2 and INF+3 respectively.
The base INF (Information Number) parameter is an IEC 60870-5-103 identifier that associates a
function in a 103 Master (such as Scada) with its equivalent in the IED.
18.8.14.2
Identification
Function description
IED commands with position and
select for IEC 60870-5-103
18.8.14.3
Function block
BLOCK
POSITION
SELECT
IEC10000286 V1 EN-US
Figure 606: I103POSCMD function block
18.8.14.4
Signals
Table 888: I103POSCMD Input signals
Name
BLOCK
POSITION
SELECT
18.8.14.5
Settings
Table 889: I103POSCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
InfNo
160 - 236
1180
I103POSCMD
IEC10000286-1-en.vsd
Type
Default
BOOLEAN
INTEGER
BOOLEAN
Unit
-
-
Function block
IEC 60617
name
identification
I103POSCMD
-
Description
0
Block of command
0
Position of controllable object
0
Select of controllable object
Step
Default
1
1
4
160
1MRK 502 066-UUS B
Report Intermediate Position =
GUID-ABF81C27-4605-4A15-9CF5-77FF82DE8747 v1
ANSI/IEEE C37.2
device number
-
GUID-3A31C1F2-1FB5-4DB0-A698-AD3F55738DB1 v1
Description
Function type
Information number for command output
Technical manual
PID-3971-INPUTSIGNALS v2
PID-6597-SETTINGS v4