Section 18
Station communication
Table 900:
INF
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
84
85
86
87
88
89
90
91
92
93
Measurands
Function blocks in monitor direction for input measurands. Typically connected to monitoring
function, for example to power measurement CVMMXN.
Measurands in public range, I103MEAS
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
1186
Description
Pickup phase A
Pickup phase B
Pickup phase C
Pickup residual current IN
Trip general
Trip phase A
Trip phase B
Trip phase C
Back up trip I>>
Fault location in ohm
Forward/line
Reverse/busbar
Signal transmitted
Signal received
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Pickup general
Breaker failure
Trip measuring system phase A
Trip measuring system phase B
Trip measuring system phase C
Trip measuring system neutral
N
Over current trip, stage low
Over current trip, stage high
Ground-fault trip, stage low
Ground-fault trip, stage high
TYP
GI
COT
2
Y
1,7,9
2
Y
1,7,9
2
Y
1,7,9
2
Y
1,7,9
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
4
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
Y
1,7,9
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
2
N
1,7
1MRK 502 066-UUS B
M11874-382 v2
M11874-385 v8
Technical manual