1MRK 502 066-UUS B
16.10.2
Functionality
The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed time
when a given binary signal has been high, see also figure 571.
BLOCK
RESET
IN
ADDTIME
tAddToTime
99 999.9 h
tWarning
tAlarm
-1
q
= unit delay
IEC15000321 V1 EN-US
Figure 571: TEILGAPC logics
The main features of TEILGAPC are:
Applicable to very long time accumulation (≤ 99999.9 hours)
Supervision of limit transgression conditions and rollover/overflow
Possibility to define a warning and alarm with the resolution of 0.1 hours
Retain any saved accumulation value at a restart
Possibilities for blocking and reset
Possibility for manual addition of accumulated time
Reporting of the accumulated time
16.10.3
Function block
BLOCK
IN
ADDTIME
RESET
IEC15000323 V1 EN-US
Figure 572: TEILGAPC function block
Technical manual
Time Accumulation
with Retain
TEILGAPC
ALARM
WARNING
OVERFLOW
ACC_HOUR
ACC_DAY
IEC15000323.vsdx
-1
q
a
&
a>b
b
a
&
a>b
b
&
a
a>b
b
IEC15000321-1-en.vsd
Section 16
Monitoring
GUID-464FB24F-B367-446C-963A-A14841943B87 v2
ACC_HOUR
ACC_DAY
OVERFLOW
WARNING
ALARM
GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1
1097