ABB RELION 670 Series Technical Manual page 503

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Name
Values (Range)
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
tReset2
0.000 - 60.000
tPCrv2
0.005 - 3.000
tACrv2
0.005 - 200.000
tBCrv2
0.00 - 20.00
tCCrv2
0.1 - 10.0
tPRCrv2
0.005 - 3.000
tTRCrv2
0.005 - 100.000
tCRCrv2
0.1 - 10.0
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
tReset3
0.000 - 60.000
tPCrv3
0.005 - 3.000
tACrv3
0.005 - 200.000
tBCrv3
0.00 - 20.00
tCCrv3
0.1 - 10.0
tPRCrv3
0.005 - 3.000
tTRCrv3
0.005 - 100.000
tCRCrv3
0.1 - 10.0
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
tReset4
0.000 - 60.000
tPCrv4
0.005 - 3.000
tACrv4
0.005 - 200.000
tBCrv4
0.00 - 20.00
tCCrv4
0.1 - 10.0
Table continues on next page
Technical manual
Unit
Step
Default
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
Description
Reset curve type for step2
(Instantaneous / IEC / ANSI)
Reset time delay for step 2
Param P for customized inverse trip time
curve for step 2
Param A for customized inverse trip time
curve for step 2
Param B for customized inverse trip time
curve for step 2
Param C for customized inverse trip time
curve for step 2
Param PR for customized inverse reset
time curve for step 2
Param TR for customized inverse reset
time curve for step 2
Param C for customized inverse reset time
curve for step 2
Reset curve type for step3
(Instantaneous / IEC / ANSI)
Reset time delay for step 3
Param P for customized inverse trip time
curve for step 3
Param A for customized inverse trip time
curve for step 3
Param B for customized inverse trip time
curve for step 3
Param C for customized inverse trip time
curve for step 3
Param PR for customized inverse reset
time curve for step 3
Param TR for customized inverse reset
time curve for step 3
Param CR for customized inverse reset
time curve for step 3
Reset curve type for step4
(Instantaneous / IEC / ANSI)
Reset time delay for step 4
Param P for customized inverse trip time
curve for step 4
Param A for customized inverse trip time
curve for step 4
Param B for customized inverse trip time
curve for step 4
Param C for customized inverse trip time
curve for step 4
Section 8
Current protection
497