14.3.6.4
Settings
Table 490: SCSWI Non group settings (basic)
Name
Values (Range)
CtlModel
Dir Norm
SBO Enh
PosDependent
Always permitted
Not perm at
00/11
tSelect
0.00 - 600.00
tResResponse
0.000 - 60.000
tSynchrocheck
0.00 - 600.00
tSynchronizing
0.00 - 600.00
tExecutionFB
0.00 - 600.00
tPoleDiscord
0.000 - 60.000
SuppressMidPos
Disabled
Enabled
InterlockChk
Sel & Op phase
Op phase
14.3.6.5
Operation principle
The Switch controller (SCSWI) is provided with verification checks for the select - execute
sequence, that is, checks the conditions prior each step of the operation are fulfilled. The involved
functions for these condition verifications are interlocking, reservation, blockings and
synchronism-check.
Control handling
.
Two types of control models can be used. The two control models are "direct with normal security"
and "SBO (Select-Before-Operate) with enhanced security". The parameter
one of the two control models is used. The control model "direct with normal security" does not
require a select whereas, the "SBO with enhanced security" command model requires a select
before execution. The command sequence for a command with control mode SBO with enhanced
security is shown in figure 437, with control mode direct with normal security is shown in figure
438.
Technical manual
Unit
Step
Default
-
-
SBO Enh
-
-
Always
permitted
s
0.01
30.00
s
0.001
5.000
s
0.01
10.00
s
0.01
0.00
s
0.01
30.00
s
0.001
2.000
-
-
Enabled
-
-
Sel & Op phase
Description
Specifies control model type
Permission to operate depending on the
position
Maximum time between select and
execute signals
Allowed time from reservation request to
reservation granted
Allowed time for synchronism-check to
fulfil close conditions
Supervision time to get the signal
synchronizing in progress
Maximum time from command execution
to termination
Allowed time to have discrepancy between
the poles
Mid-position is suppressed during the
time tIntermediate
Selection if interlock check should be done
in select phase
CtlModel defines which
Section 14
Control
PID-6500-SETTINGS v3