Section 18
Station communication
Name
Values (Range)
MV hLim
-5000.00 -
5000.00
MV lLim
-5000.00 -
5000.00
MV llLim
-5000.00 -
5000.00
MV min
-5000.00 -
5000.00
MV max
-5000.00 -
5000.00
MV dbType
Cyclic
Dead band
Int deadband
MV limHys
0.000 - 100.000
18.4.6.5
Monitored data
Table 819: MVGAPC Monitored data
Name
VALUE
RANGE
18.4.6.6
Operation principle
Upon receiving an analog signal at its input, Generic communication function for Measured Value
(MVGAPC) will give the instantaneous value of the signal and the range, as output values. In the
same time, it will send over IEC 61850-8-1 the value, to other IEC 61850 clients in the substation.
18.4.7
IEC 61850-8-1 redundant station bus communication
Function description LHMI and ACT
Dual ethernet port
link status
IEC 62439-3 parallel
redundancy
protocol
1120
Unit
Step
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
-
-
%
0.001
Type
Values (Range)
REAL
-
INTEGER
1=High
2=Low
3=High-High
4=Low-Low
0=Normal
IEC 61850
identification
identification
PRPSTATUS
PRPSTATUS
PRP
PRP
Default
Description
800.00
High limit multiplied with the base prefix
(multiplication factor)
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
-900.00
Low Low limit multiplied with the base
prefix (multiplication factor)
-1000.00
Minimum value multiplied with the base
prefix (multiplication factor)
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
Dead band
Reporting type
5.000
Hysteresis value in % of range (common
for all limits)
Unit
Description
-
Magnitude of deadband value
-
Range
IEC 60617
identification
-
-
1MRK 502 066-UUS B
PID-3779-MONITOREDDATA v5
SEMOD55936-5 v6
GUID-FF43A130-7D2D-4BA3-B51C-80398D73228F v2
GUID-00C469E6-00D4-4780-BD0D-426647AB8E0F v3.1.1