ABB RELION 670 Series Technical Manual page 898

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
Name
MASTER
FOLLOWER
MFERR
OUTOFPOS
VGTUPPDB
VLTLOWDB
COMMERR
ICIRC
TRFDISC
VTALARM
T1PG
T2PG
T3PG
T4PG
T5PG
T6PG
T7PG
T8PG
Table 523: TCMYLTC (84) Input signals
Name
YLTCIN
TCINPROG
INERR
RESETERR
OUTERR
RS_CLCNT
RS_OPCNT
PARITY
BIERR
B1
B2
B3
B4
B5
B6
MA
892
Type
Description
BOOLEAN
The transformer is master
BOOLEAN
This transformer is a follower
BOOLEAN
The number of masters is different from one
BOOLEAN
To high difference in tap positions
BOOLEAN
Voltage greater than deadband-high, ULOWER command to come
BOOLEAN
Voltage lower than deadband-low, URAISE command to come
BOOLEAN
Communication error
BOOLEAN
Block from high circulating current
BOOLEAN
The transformer is disconnected
BOOLEAN
VT supervision alarm
BOOLEAN
Transformer1 included in parallel group
BOOLEAN
Transformer2 included in parallel group
BOOLEAN
Transformer3 included in parallel group
BOOLEAN
Transformer4 included in parallel group
BOOLEAN
Transformer5 included in parallel group
BOOLEAN
Transformer6 included in parallel group
BOOLEAN
Transformer7 included in parallel group
BOOLEAN
Transformer8 included in parallel group
Type
Default
Description
GROUP
-
Input group connection for YLTC
SIGNAL
BOOLEAN
0
Indication that tap is moving
BOOLEAN
0
Supervision signal of the input board
BOOLEAN
0
Reset of command and tap error
BOOLEAN
0
Supervision off the digital output board
BOOLEAN
0
Reset of the contact life counter
BOOLEAN
0
Resets the operation counter
BOOLEAN
0
Parity bit from tap changer for the tap position
BOOLEAN
0
Error bit from tap changer for the tap position
BOOLEAN
0
Bit 1 from tap changer for the tap position
BOOLEAN
0
Bit 2 from tap changer for the tap position
BOOLEAN
0
Bit 3 from tap changer for the tap position
BOOLEAN
0
Bit 4 from tap changer for the tap position
BOOLEAN
0
Bit 5 from tap changer for the tap position
BOOLEAN
0
Bit 6 from tap changer for the tap position
REAL
0
mA from tap changer for the tap position