ABB RELION 670 Series Technical Manual page 1184

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 18
Station communication
18.8.12.5
Settings
Table 884: I103USRCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
PulseMode
Steady
Pulsed
PulseLength
0.200 - 60.000
InfNo_1
1 - 255
InfNo_2
1 - 255
InfNo_3
1 - 255
InfNo_4
1 - 255
InfNo_5
1 - 255
InfNo_6
1 - 255
InfNo_7
1 - 255
InfNo_8
1 - 255
18.8.13
Function commands generic for IEC 60870-5-103 I103GENCMD
18.8.13.1
Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The function has
two outputs signals CMD_OFF and CMD_ON that can be used to implement double-point
command schemes.
The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2 steady ON/OFF
outputs. The ON output is pulsed with a command with value 2, while the OFF output is pulsed
with a command value 1. If in steady mode is ON asserted and OFF deasserted with command 2
and vice versa with command 1. Steady mode is selected by setting PulseLength=0. The
I103GENCMD is retained, and a command in steady mode will be reissued on restart.
18.8.13.2
Identification
Function description
Function commands generic for IEC
60870-5-103
1178
Unit
Step
Default
-
1
1
-
-
Pulsed
s
0.001
0.400
-
1
1
-
1
2
-
1
3
-
1
4
-
1
5
-
1
6
-
1
7
-
1
8
Function block
name
I103GENCMD
Description
Function type (1-255)
Pulse mode
Pulse length
Information number for output 1 (1-255)
Information number for output 2 (1-255)
Information number for output 3 (1-255)
Information number for output 4 (1-255)
Information number for output 5 (1-255)
Information number for output 6 (1-255)
Information number for output 7 (1-255)
Information number for output 8 (1-255)
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
1MRK 502 066-UUS B
PID-3790-SETTINGS v4
GUID-729E9AFD-0468-4BBD-B54A-A6CDCC68A9B2 v3
GUID-1933A30C-5214-4116-8CD3-91BD975FACED v1
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670