ABB RELION 670 Series Technical Manual page 1200

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 18
Station communication
Name
APP11_OP
APP11_CL
APP11VAL
APP12_OP
APP12_CL
APP12VAL
APP13_OP
APP13_CL
APP13VAL
APP14_OP
APP14_CL
APP14VAL
APP15_OP
APP15_CL
APP15VAL
COMMVALID
TEST
18.9.4
Settings
Table 906: GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
18.9.5
Operation principle
The APPxVAL output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Table continues on next page
1194
Type
Description
BOOLEAN
Apparatus 11 position is open
BOOLEAN
Apparatus 11 position is closed
BOOLEAN
Apparatus 11 position is valid
BOOLEAN
Apparatus 12 position is open
BOOLEAN
Apparatus 12 position is closed
BOOLEAN
Apparatus 12 position is valid
BOOLEAN
Apparatus 13 position is open
BOOLEAN
Apparatus 13 position is closed
BOOLEAN
Apparatus 13 position is valid
BOOLEAN
Apparatus 14 position is open
BOOLEAN
Apparatus 14 position is closed
BOOLEAN
Apparatus 14 position is valid
BOOLEAN
Apparatus 15 position is open
BOOLEAN
Apparatus 15 position is closed
BOOLEAN
Apparatus 15 position is valid
BOOLEAN
Communication Valid
BOOLEAN
Test Output
Unit
Step
-
-
Data Value
Updated
0
0
0
0
Default
Description
Disabled
Operation Disabled/Enabled
Data Valid
1
0
0
0
0
1MRK 502 066-UUS B
SEMOD173207-1 v2
PID-3784-SETTINGS v4
GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
Technical manual