ABB RELION 670 Series Technical Manual page 1116

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 17
Metering
RSTACC
EAFPrestVal
ACCINPRG
P* (ACTIVE FORWARD)
1000 GWh
-1
q
= unit delay
IEC13000187 V5 EN-US
Figure 579: Logic for integration of active forward energy
The energy pulses generated by using internally calculated accumulated energy values and energy
per pulse (
pulse value to get the number of pulses. The number of pulses can be reset to zero by activating
RSTACC input or by using the local HMI reset menu. The pulse on and off time duration is set by the
settings
for the integrated energy in the active forward direction. Similarly, the pulse generation for
integrated energy in the active reverse, reactive forward and reactive reverse is done.
1110
X
60.0
-1
q
a
a>b
b
ExxAccPlsQty ) setting. The accumulated energy values are divided by the energy-per-
tEnergyOnPls and tEnergyOffPls .
T
T
F
F
&
-1
q
T
F
0.0
Figure 580
shows the logic for pulse output generation
1MRK 502 066-UUS B
EAFACC
IEC13000187-5-en.vsdx
Technical manual