ABB RELION 670 Series Technical Manual page 1221

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Name
Values (Range)
CommSync
Slave
Master
OptoPower
LowPower
HighPower
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
ComFailAlrmDel
5 - 500
ComFailResDel
5 - 500
RedChSwTime
5 - 500
RedChRturnTime
5 - 500
AsymDelay
-20.00 - 20.00
AnalogLatency
2 - 20
remAinLatency
2 - 20
MaxTransmDelay
0 - 40
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
MaxtDiffLevel
200 - 2000
DeadbandtDiff
200 - 1000
InvertPolX21
Disabled
Enabled
Table 936: LDCMRecBinStat3 Non group settings (basic)
Name
Values (Range)
ChannelMode
Blocked
Normal
OutOfService
TerminalNo
0 - 255
RemoteTermNo
0 - 255
DiffSync
Echo
GPS
GPSSyncErr
Block
Echo
CommSync
Slave
Master
Table continues on next page
Technical manual
Unit
Step
Default
-
-
Slave
-
-
LowPower
-
-
CT-GRP1
ms
5
100
ms
5
100
ms
5
5
ms
5
100
ms
0.01
0.00
-
1
2
-
1
2
ms
1
20
-
-
0-25kA
us
1
600
us
1
300
-
-
Disabled
Unit
Step
Default
-
-
Normal
-
1
0
-
1
0
-
-
Echo
-
-
Block
-
-
Slave
Remote communication
Description
Com Synchronization mode of LDCM,
0=Slave, 1=Master
Transmission power for LDCM, 0=Low,
1=High
Summation mode for transmitted current
values
Time delay before communication error
signal is activated
Reset delay before communication error
signal is reset
Time delay before switching in redundant
channel
Time delay before switching back from
redundant channel
Asymmetric delay when communication
use echo synch.
Latency between local analogue data and
transmitted
Analog latency of remote terminal
Max allowed transmission delay
Compression range
Maximum time diff for ECHO back-up
Deadband for t Diff
Invert polarization for X21 communication
Description
Channel mode of LDCM, 0=OFF, 1=ON,
2=OutOfService
Terminal number used for line differential
communication
Terminal number on remote terminal
Diff Synchronization mode of LDCM,
0=ECHO, 1=GPS
Operation mode when GPS synchroniation
signal is lost
Com Synchronization mode of LDCM,
0=Slave, 1=Master
Section 19
PID-3874-SETTINGS v5
1215

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670